Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
198
Operating Instructions, 02/2018, C79000-G8976-C468-02
Range of
values:
See address range
Default:
0 (B#16#0)
Address
range:
Output
QB0 … QBn
PQB0 … PQBn
Memory bit
MB0 … MBn
LB0 … LBn
Data
DBm.DBB0 … n
Explanation: Currentness status of a received data segment
During receipt of a sequence, the current status is indicated by the "DataSta-
tus" output byte:
•
If the receipt of the sequence was completed successfully, the
"DataOutput" data output area is up-to-date. The status bit "DataValid" is
set to TRUE.
If "SendAll" is set to TRUE on the sender, the data is consistent.
•
If the receipt of a sequence is disrupted, the "DataOutput" data output area
is not up-to-date and "DataStatus" indicates an error.
–
The status bit "DataValid" is set to FALSE and an entry is written to the
diagnostics buffer.
–
The "SequenceState" status shows the error (see table).
Table 5- 7
Bit assignment of "DataStatus"
Bit
Name
Value
Meaning
0
DataValid
FALSE
Data invalid
TRUE
Data valid
1 ... 5 Reserved
- (FALSE)
Not used
7, 6
SequenceState
0
No data being received or receipt completed without
error.
1
First segment of a sequence received
2
Second or higher segment of a sequence received
3
Errors:
•
Transmission sequence aborted
•
Monitoring time exceeded
•
Other error receiving
5.7.1.18
Parameter typical Par12D_S
Function
Send 1 to 12 parameter values (each 1 double word) and receive the current, locally valid
parameter values from the partner.
The 1-out-of-n check is performed by FC Safe.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...