Configuration
4.13 Communication with the CPU
TIM 1531 IRC
82
Operating Instructions, 02/2018, C79000-G8976-C468-02
●
Max. number of read jobs
Maximum number of low-priority read jobs from the CPU memory area within a CPU scan
cycle.
●
Frame memory size
Here, you set the size of the frame memory for events (send buffer).
The size of the frame memory is divided equally among all configured communications
partners. You will find the size of the frame memory in the section Performance data and
configuration limits (Page 25).
You will find details of how the send buffer works (storing and sending events) as well as
the options for transferring data in the section Process image, type of transmission, event
Watchdog bit
●
TIM monitoring
Via the watchdog bit the CPU can be informed of the status of the telecontrol
communication of the TIM.
PLC tags for partner status / path status
Via the PLC tag that can be configured here, you can monitor the following information about
the reachability of the communications partners:
●
Partner status
Reachability of the remote communications partner
●
Path status
Status of the connection path or the redundant connection paths to the remote
communications partner
For the communication response of the two connection paths see section Communication
via the SINAUT ST7 protocol (Page 56).
For every configured communications partner to which a single or redundant telecontrol
connection is created, you can create a PLC tag of the type Word.
Assignment of the PLC tags for partner status / path status
In the two bytes of the PLC tag of the data type Word (DB, memory bit, output) the following
information is output:
●
Byte 0: Partner status
●
Byte 1: Path status
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...