Application and functions
1.7 Performance data and configuration limits
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
25
1.7
Performance data and configuration limits
Connection resources
●
Telecontrol connections
The number of connections or communications partners is limited for the two interface
types and every individual interface.
The maximum number of connections or communications partners depends on the
network node type with which the interface is set.
Network
node type
Interface
Max. number per
interface type
Network
type
Max. number of connections /
partners per interface
Master
station
Ethernet X1
128
TCP
•
62 S7 connections
or
•
127 MSC connections
Ethernet X2
62 S7 connections
Ethernet X3
62 S7 connections
Serial X4
32
Dedicated
line
32 partners
Dialup
network
32 partners
Node /
station
Ethernet X1
32
TCP
•
16 S7 connections
or
•
1 MSC connection
Ethernet X2
16 S7 connections
Ethernet X3
16 S7 connections
Serial X4
16
Dedicated
line
16 partners
Dialup
network
16 partners
●
E-mail / SMS
At runtime, a connection can be established to send an e-mail or SMS message.
●
S7 connections
–
When using ST7 communication:
66 connection resources in total incl. telecontrol connections (see above) and max. 4
PG/OP connections (see below)
–
Without using ST7 communication:
4 connection resources only for PG/OP connections (see below)
●
PG/OP connections
4 connection resources for connections to the engineering station or HMI devices
(included in the configuration limits of the S7 connections, see above)
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...