5.7 Master copies
TIM 1531 IRC
196
Operating Instructions, 02/2018, C79000-G8976-C468-02
Parameter: MonitoringTime
Declaration: INPUT
Data type:
INT
Range of
values:
0 (no limit) / 1 … 32000 (seconds)
Default:
0
Explanation: Maximum time for a complete response to a single request
Each time a single request starts (see SingleRequest parameter), the time
specified here is started in "SingleRequest".
If a value higher than 0 is entered and the time for the response sequence is
exceeded, an error is indicated via the "DataStatus" output byte (status bits
"SequenceState"). Apart from this an entry is written to the diagnostics buffer
(event ID B13CTD7_Diagnostics).
Each time a single request starts, "MonitoringTime" is reactivated.
Parameter: DataOutput
Declaration: INTPUT
Data type:
ANY
Range of
values:
See address range
Default:
P#P 0.0 VOID 0
(null pointer)
Address
range:
P#DBxx.DBX yy.0 DWORD zz
•
xx: Data block number 1...32767
•
yy: Byte number
•
zz: Number of double words 1...256 starting at byte number yy
Example:
P#DB20.DBX 100.0 DWORD 200
Remember the periods and spaces when entering the pointer!
Note that the default value (null pointer) is not permitted. A pointer with a real
address must be specified.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...