5.7 Master copies
TIM 1531 IRC
146
Operating Instructions, 02/2018, C79000-G8976-C468-02
•
Receiving operator typicals
(Bin04B_R, Ana04W_R, Cnt01D_R/Cnt04D_R, Dat12D_R, Dat256D_R)
The value 0 is not permitted!
If PartnerNo is < 1 or > 32000, an error message is entered in the
diagnostic buffer (event ID B100).
If the programmed value is permitted and correct but "PartnerNo" is not
found in the administration (DB BasicData), an entry is also made in the
diagnostics buffer (event ID B101). The CPU does not change to STOP.
The block is then no longer processed, however, until the error in the
programming has been corrected.
If the CPU receives a data frame for this typical, a check is made to
establish whether source subscriber number in the data frame is identical
to the "PartnerNo" programmed here. If the two subscriber numbers are
different, the received information is discarded and an error message is
entered in the diagnostic buffer (Event ID B130).
•
Sending operator typicals
(Cmd01B_S, Set01W_S, Par12D_S)
The value 0 is not permitted!
If "PartnerNo" is < 1 or > 32000, an error message is entered in the
diagnostic buffer (event ID B100).
If the programmed value is permitted and correct but "PartnerNo" is not
found in the administration (DB BasicData), an entry is also made in the
diagnostics buffer (event ID B101). The CPU does not change to STOP.
The block is then no longer processed, however, until the error in the
programming has been corrected.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...