Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
212
Operating Instructions, 02/2018, C79000-G8976-C468-02
Address
range:
P#DBxx.DBX yy.0 DWORD zz
•
xx: Data block number 1...32767
•
yy: Byte number
•
zz: Number of double words 1...12 starting at byte number yy
Example:
P#DB20.DBX 100.0 DWORD 4
Remember the periods and spaces when entering the pointer!
Note that the default value (null pointer) is not permitted. A pointer with a real
address must be specified.
Explanation: Local parameter input area
The ANY pointer addresses the data area in which the parameter values to be
acquired are located. This data area must be within a data block and its length
can vary between 1 and 12 data double words. The length must be identical to
the length specified for" ParameterOutput".
For information on the content and formats, refer to the section "Function"
above.
If the parameter assignment is incorrect (null pointer, length > 12, data area
not a DB), an error message is entered in the diagnostics buffer (event ID
B114, [Info2/3] = 11). The CPU does not change to STOP. The block is then
no longer processed, however, until the error has been corrected.
If you do not require the parameter, simply leave it open.
Parameter: ParameterOutput
Declaration: INPUT
Data type:
ANY
Range of
values:
See address range
Default:
P#P 0.0 VOID 0
(null pointer)
Address
range:
P#DBxx.DBX yy.0 DWORD zz
•
xx: Data block number 1...32767
•
yy: Byte number
•
zz: Number of double words 1...12 starting at byte number yy
Example:
P#DB20.DBX 100.0 DWORD 4
Remember the periods and spaces when entering the pointer!
Note that the preset value (null pointer) is not permitted. A pointer with a real
address must be specified.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...