Configuration
4.13 Communication with the CPU
TIM 1531 IRC
84
Operating Instructions, 02/2018, C79000-G8976-C468-02
Table 4- 2
Assignment of byte 1:
Bits 6 + 7
Bits 4 + 5
Bits 2 + 3
Bits 0 + 1
Configured interface
Path status
Coding for substitute path
Coding for main path
Substitute path (2nd
path)
Main path (1st path)
●
Configured interface
The TIM interfaces "Ethernet 1" (IE1), "Ethernet 2" (IE2), "Ethernet 3" (IE3) and WAN1
are numbered through from 0 . 3 (decimal):
–
0 = Ethernet interface IE1 (X1)
–
1 = Ethernet interface IE2 (X2)
–
2 = Ethernet interface IE3 (X3)
–
3 = Serial interface WAN1 (X4)
Status of bit 5
(7)
Status of bit 4
(6)
Meaning
0
0
Coding for Ethernet interface X1 (decimal: No. 0)
0
1
Coding for Ethernet interface X2 (decimal: no. 1)
1
0
Coding for Ethernet interface X3 (decimal: no. 2)
1
1
Coding for serial interface X4 (decimal: no. 3)
●
Path status
–
Main path = 1. Path (bits 0 + 1)
–
Substitute path = 2nd path (bits 2 + 3)
Status of bit
1 (3)
Status of bit
0 (2)
Meaning bit 1
Meaning bit 0
0
0
Bit 1: Path not current
Bit 0: Subscriber not reachable
0
1
Bit 1: Path not current
Bit 0: Subscriber reachable
1
0
Bit 1: Path current
Bit 0: Subscriber not reachable
1
1
Bit 1: Path current
Bit 0: Subscriber reachable
Coding options of byte 1
Same coding of the configured interface for the main and the substitute path means that
there is no path redundancy (only one interface configured). The path status is output via the
bits of the main path (1st path).
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...