Configuration
4.22 Data points
TIM 1531 IRC
126
Operating Instructions, 02/2018, C79000-G8976-C468-02
Note
Evaluation of the value even when the option is disabled
If you enable one or both options and configure a value and then disable the option later, the
grayed out value is nevertheless evaluated.
To disable the two options, delete the previously configured values limit values from the input
boxes and then disable the relevant option.
Recommendation for quickly fluctuating analog values:
If the analog value fluctuates quickly, it may be useful to smooth the analog value first if limit
values are configured.
4.22.9
Command output
Parameters for the data point type "Command output (Cmd01B_R)"
The following output options can alternatively be assigned to a data point of the type
"Command output (Cmd01B_R)":
●
LATCH_ON/OFF
The function permanently latches the command output to the value 1.
Note:
The latched value is only canceled by a new command. Alternatively, the command can
be reset by the user program.
●
PULSE_ON/OFF
The function evaluates the "Command output time" for the command output of the data
point.
Parameter
Name:
Max. number of pulses
Range of val-
ues:
1
Explanation: Only a single received pulse is evaluated. If the number of pulses received
exceeds the value 1, the command is discarded.
Name:
Command output time (s)
Range of val-
ues:
0 ... 65535
Default:
0
Explanation: Period for which the command is output.
Only for the "PULSE_ON/OFF" option.
When the time expires, the output is automatically reset.
With zero, a set command output is not automatically reset. In this case, you
need to reset the output via the user program.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...