Diagnostics and upkeep
7.3 Update firmware
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
285
Loading the firmware with the online functions of STEP 7 via Ethernet / Internet
Requirements:
●
The TIM can be reached using an IP address.
●
The engineering station and the TIM are located in the same subnet.
●
The new firmware file is stored on your engineering station.
●
The engineering station is connected to the network.
●
The relevant STEP 7 project is open on the engineering station.
Procedure:
1.
Select the TIM that you want to update with new firmware.
2.
Enable the online functions using the "Connect online" icon.
3.
In the "Connect online" dialog, select the Ethernet interface in the "Type of PG/PC
interface" list box.
4.
Select the TIM.
5.
Click on "Start search" to search for the module in the network and to specify the
connection path.
When the module is found it is displayed in the table.
6.
Connect using the "Connect" button.
The "Connect online" wizard guides you through the remaining steps in installation.
7.
In the network view, select the TIM and select the "Online & Diagnostics" shortcut menu
(right mouse button).
8.
In the navigation panel of the Online & Diagnostics view select the entry "Functions >
Firmware update".
9.
Using the "Browse" button (parameter group "Firmware loader") search for the new
firmware file in the file system of the engineering station.
10.Start to download the firmware with the "Start update" button when the correct version of
the signed firmware is displayed in the "Status" output box.
You will find further information on the online functions in the STEP 7 information system.
Loading the firmware via the SD card
Requirements:
●
You have copied the new firmware file from your PC to the SD card using a suitable card
reader.
●
You have saved a backup file of the firmware file currently being used.
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...