Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
190
Operating Instructions, 02/2018, C79000-G8976-C468-02
Explanation: Send on change
With the setting TRUE, the block runs a change check within the acquired
data area "DataInput". The block checks whether at least one bit has
changed. If a change is detected, a transfer of the data area is started auto-
matically. You specify whether the entire area is transferred or only the
changed part with the "SendAll" parameter.
If the setting is FALSE, you need to trigger the transfer via the input parameter
"TriggerInput".
Parameter: TriggerInput
Declaration: INPUT
Data type:
BOOL
Range of
values:
TRUE / FALSE
Default:
FALSE
Address
range:
Input
I 0.0 ... I n.7
Memory bit
M 0.0 ... M n.7
L 0.0 ... L n.7
Data bit
DBm.DBX 0.0 ... n.7
Explanation: Trigger input
With the edge change 0
→
1 of the "TriggerInput" input, the transfer of the data
frame can be triggered at a required time.
Example:
Time-driven analog value transfer with time stamp for supplying an analog
value archive in the control center.
The FC Trigger block can be used for time-driven triggering of a transmission
over "TriggerInput".
"TriggerInput" actually only triggers transmission indirectly. With a 0
→
1 edge
change at "TriggerInput", the data frame is put together with its current values
and transferred to the local TIM. The TIM is responsible for the actual trans-
mission to the partner. With dedicated lines or wireless networks the transfer
is immediate. With a dial-up connection, it is possible that the data frame is
saved first on the TIM and sent at a later point in time. The reason can, for
example, be that the data frame is marked as "Conditional spontaneous", see
parameter "Conditional".
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...