Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
235
One bit per subscriber is reserved in the "PartnerStatus" output byte to indicate the status of
the respective subscriber:
●
FALSE (0):
–
Subscriber disrupted
–
Corresponding input parameter not used (= 0)
–
Subscriber unknown
●
TRUE (1): Subscriber OK
Parameter
Name:
Partner1 ... Partner8
Declaration: INPUT
Data type:
INT
Range of
values:
•
0
Value for unrequired parameter
•
1 ... 32000
Number of the subscriber to be monitored
Explanation
SINAUT subscriber number of the subscriber to be monitored
If a set subscriber number is not found in the administration (DB BasicData),
then (only during startup) an entry is written to the diagnostics buffer (event ID
B101). The CPU does not change to STOP.
The status of a subscriber with a correct parameter assignment is indicated in
the "PartnerStatus" output byte.
An unknown subscriber is not processed until the error is eliminated. Their
status bits are set to 0.
Name:
PartnerStatus
Declaration: OUTPUT
Data type:
BYTE
Range of val-
ues:
Output bytes
QB0 ... QBn
PQB0 ... PQBn
Memory bytes
MB0 ... MBn
LB0 ... LBn
Data bytes
DBm.DBB0 ... n
Explanation: Indication of the status of the subscriber to be monitored.
Assignment of the status bits in the "PartnerStatus" output byte depending
the parameters Partner1 ... "Partner8":
Bit
.7
.6
.5
.4
.3
.2
.1
.0
Partner
8
7
6
5
4
3
2
1
Value:
•
0 = partner disrupted, not set in the parameters or unknown
•
1 = partner OK
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...