Block library TeleControl ST7
5.7 Master copies
TIM 1531 IRC
236
Operating Instructions, 02/2018, C79000-G8976-C468-02
5.7.2.4
FC PathStatus
Function
The block (FC) shows the status of the path to a partner from the perspective of the local
TIM.
A maximum of 2 paths (main and substitute path) to a partner can be configured. Both paths
must begin or end on a local TIM.
The block shows the following:
●
The paths via which the partner can be reached.
●
The path currently being used
●
The TIM interface via which the main path was configured.
●
The TIM interface via which the substitute path was configured.
The path of a connection is specified as a combination of the used interfaces of the TIM and
the status of the path.
In the output byte PathStatus the following bits are reserved:
●
Two bits for the interface of the main path
●
Two bits for the interface of the substitute path
●
Two bits for the status of the main path
●
Two bits for the status of the substitute path
The FC can be called at any point in the cyclic user program (OB1) after calling the FC
BasicTask.
If the status of the path to more than one subscriber is to be shown, a corresponding number
of FC calls need to be programmed in the user program program.
Parameter
Name:
Partner
Declaration: INPUT
Data type:
INT
Range of
values:
1 ... 32000 (subscriber number)
Explanation: SINAUT subscriber no. of the partner
Name:
PathStatus
Declaration: OUTPUT
Data type:
BYTE
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...