Diagnostics and upkeep
7.4 Resetting to factory settings
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
287
7.4
Resetting to factory settings
Resetting to factory settings: Effect
Note
Configuration data is deleted
With the functions for resetting to factory settings described here, all configuration data on
the TIM is deleted!
●
Deleted data
The following data is deleted by resetting to factory settings:
–
Configured IP addresses of the LAN interfaces X1 X2 and X3
–
All other configuration data in the work memory of the TIM
●
Data not deleted
The following data is not deleted by resetting to factory settings:
–
MAC addresses of the LAN interfaces
Note
Configuration data when using an SD card
If you use an SD card and you want to reset the TIM to the factory settings, you must pull the
SD card before resetting. If the SD card remains inserted, the TIM starts up again with the
configuration data on the SD card.
When pulling the SIM card, remember the information in section Inserting the SD card
(Page 47).
Executing the "Reset to factory settings" function
To reset to factory settings using the switch, follow the steps outlined below:
1.
Put the switch to the position "MRES" and hold it in the "MRES" position for at least 5
seconds.
The TIM restarts.
2.
During the restart, continue to hold the switch in the "MRES" position.
If the LED pattern of step 2 occurs (see below) the TIM is reset.
For information on the switch settings, refer to the section Switch (Page 35).
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...