8.3.1
Activate block
Activate the rotary step switch by assigning command
or
load to output A.
Do this via the motor block to be connected, the logic block
or
the continuous
output, i.e. from their configuration menus.
See the following example:
Command of output A is to act on Logic block 1.
Example
Main menu > Commissioning > Extra configuration > Aggregates > Logic functions > Logic
1...10 >
Configuration
Operating line
Setting (example)
[Logic A] input 1
[Rot step swi 1A] command
Note the following for output switching:
Configure the outputs without gap (order A,B,C,D).
Assign the smallest load to command A in the event of different loads.
Use the type ("Linear", "Flexible", "Binary") to set the step switch properties.
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1…2 >
Configuration
Operating line
Range
Factory setting
Type
Linear, Flexible, Binary
Linear
79 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Aggregates
01.04.2010