3.5
Exit commissioning
If the application is valid, quit the Commissioning menu as follows:
–
Press the ESC button.
The display shows a dialog box with the following information:
Caution!
Plant starts
ESC
OK
–
Press the OK knob to confirm.
RMS705B boots using the settings, the plant is started, and the main menu is
displayed.
Main menu
Commissioning...
[Time swi 1] op sel...
Time switch 1...
Op selector 2...
3.6
Data backup
The entire commissioning data set (configuration and all settings) can be saved in
RMS705B after commissioning. Use this function to restore the proper controlled
state of the RMS705B after commissioning if important values are changed later
on.
The following values are
not
saved or restored during backup:
All user-defined texts and business cards.
Calendar and time switch settings.
Basic settings in the "Communication" menu.
Current time.
Trend settings.
Values in the "Settings > Device" menu.
Main menu > Data backup >
Setting values
Operating line
Range
Factory setting
Restore
Save
Main menu > Data backup >
Display values
Operating line
Comment
Storage date
Displayed date when the commissioning data set was
written in the device’s memory.
Storage year
Displayed year when the commissioning data set was
written to the device's memory.
21 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Commissioning
01.04.2010