8.1.1
Activate the logic
Activate the logic by configuring at least 1 input
or
the operation selector.
Use menu "Extra configuration" to configure logic functions for Logic A, B, and C.
The "Operation selector" setting in the operating line selects if the operation
selector is to be displayed in the main menu at the user level.
The operation selector allows users manual manipulations. No warning is
displayed during manual manipulations.
Note
Main menu > Commissioning > Extra configuration > Aggregates > Logic functions > Logic
1...10 >
Configuration
Operating line
Adjustable values
Factory setting
[Logic A] input 1
---, X1, X2, ...
---
[Logic A] input 2
---, X1, X2, ...
---
[Logic A] input 3
---, X1, X2, ...
---
[Logic B] input 1
---, X1, X2, ...
---
[Logic B] input 2
---, X1, X2, ...
---
[Logic A] function
AND, NAND, OR, NOR
OR
[Logic B] function
AND, NAND, OR, NOR
NOR
[Logic C] function
AND, NAND, OR, NOR, EXOR, EXNOR
AND
Logic relay
---, N.Q1, N.Q2, .../ (free outputs only)
---
Operation selector
Yes, No
No
Time format
h:m, m:s
m:s
You can select format "Hours:Minutes" as an extended time format (> 59.59 m.s)
for the logic function.
Important: The changeover impacts all time-related parameters of the logic
function block (switch-on/off delay and min. switch-on/off time).
Notes
Time format "h:m" offers a 10-minute increment setting range.
8.1.2
Assign texts
You can assign a specific text to each logic and operation selector. The text is
displayed on the menu and in the operating line.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Aggregates > Logic functions > Logic 1...10 >
Operating line
Range
Factory setting
Logic 1...10
Max. 20 characters
Logic 1...10
Operation selector 1...10
Max. 20 characters
Operation selector 1...10
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
69 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Aggregates
01.04.2010