6.1.3
Trend function settings
Main menu > Settings > Data acquisition > Trend > Trend channel 1...4 >
Settings
Operating line
Adjustable values / Comment
Trend channel 1…
Trend channel 4
Channel name
(editable text, max.20 characters).
Trend signal
Trend signal assignment:
---, Room temp via bus, Outside temp via bus,
N.X1 … RMZ788 (2).X4
Geographical zone
(apartment)
1…126
(relevant only if "Room temp via bus" is set).
Geographical zone
(room)
1…63
(relevant only if "Room temp via bus" is set).
Outside temperature
zone
1…31
(relevant only if "Outside temp via bus" is set).
Y-axis min
Depending on selected type.
Y-axis max
Depending on selected type.
Selection extra channel
Trend channel 1 … Trend channel 4
A trend channel is activated by assigning a "Trend signal" to it.
Explanation on the
settings
Each trend channel can be assigned a plant-specific text with max. 20
characters via operating line "Trend channel 1..4".
The bus address of the room for which the room temperature is to be recorded
can be set via the "Geographical zone".
To acquire the outside temperature via bus, set the relevant "Outside
temperature zone".
The Y-axes can be scaled for each trend channel. "Y-axis min" and "Y-axis max"
refer to value display and must be set as per the expected signal range. There is
no trend display if the current values are outside the adjusted range!
You can show a second trend channel via "Selection extra channel".
This channel is displayed as a dotted line.
As only every second measured value is displayed for the extra channel, the
value to be measured should be put on the main channel.
Notes on the
extra channel
The Y-axis label only refers to the primary channel. The extra channel is
displayed according to its Y-axis settings. If the axes differ, a warning triangle is
displayed next to the axis.
Query the trend channels via the following menu:
Display values
Main menu > Data acquisition > Trend channel 1...4 >
44 / 216