The individual settings have the following effect:
Entry Effect
Diagram
Autonomous
The holidays/special day program only acts locally on this RMS705B.
The holidays/special day program has no impact on the
holiday/special day zone entered via communication.
Slave
The holidays/special day program in this RMS705B is not active.
The external holidays/special day program with the same holidays /
special day zone is active.
The external holidays/special day program must be set as the master
holiday/special day program.
Master
The holidays/special day program in this RMS705B is active.
The holidays/special day program also acts on all other controllers
with holidays/special day programs switched off (slave) in the same
holidays/special day zone.
31
2
3
Z
0
7
See Section 13 "Communication" for "Holidays/special day zone" settings.
7.2.2
Holidays
Holidays are periods of time when the building is not used and whose start time
and duration are known in advance.
Business holidays/vacation in commercially used spaces and buildings.
Examples
School holidays/vacation in school buildings.
Public holidays.
During vacation/holidays, the output of the corresponding time switch is set to Off
(provided "Holiday priority: Yes).
7.2.3
Special days
Special days are periods of time when the building is used for special purposes
and whose start time and duration are known in advance.
Visitor days in special facilities.
Examples
Religious holidays in churches.
The 7-day program allows for an additional 24-hour program (special day) as a
special day program.
See section 7.1.2 for settings.
You can enter a specific 7-day program as a special day on each controller (slave)
if RMS705B (master) is connected to other controllers (slaves) via communication.
The time of the special day is communicated by the master and applies to all
controllers in the same holidays/special day zone.
Note
64 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
7-day time switch
01.04.2010