If a common clock time is to be used in the system, one device must be defined as
"Master", all other devices as "Slave".
Clock time operation
When set to "Autonomous", the device
neither
sends
nor
receives the clock time.
"Remote setting clock slave" = Yes allows for adjusting the clock time at the slave.
The time is sent to the master and transmitted to all other devices.
Remote setting clock
slave
You can set if self-holding fault messages can be unlocked remote
or
if unlocking
must take place via the local button. The default setting does not allow for "Remote
reset of fault".
Remote reset of fault
When device communications is enabled, the effects are:
Reasons
Fault messages are always sent via KNX bus and can be further processed by
other Synco devices.
Fault messages from other Synco devices are displayed under:
Main menu > Faults > Fault status message bus.
Fault messages from other Synco devices can be sent to a fault relay (see Section
12.5).
All fault messages can be acknowledged from remote, e.g. via operator station with
OCI700.1.
13.2.2 Holidays/special days
Main menu > Commissioning > Communication > Holidays/special days >
Setting values
Operating line
Range
Factory setting
Holidays/special day operation Autonomous,
slave,
master.
Autonomous
Holidays/special day zone
1…31
1
13.2.3 Time switch
Main menu > Commissioning > Communication > Time switch > Time switch 1…6 >
Setting values
Operating line
Range Factory
setting
Time switch operation
Autonomous, slave
Autonomous
Time switch slave (apartment)
1…126
1
Transformation Precomfort
Off, On.
On.
13.2.4 Distribution zones
Main menu > Commissioning > Communication > Distribution zones >
Setting values
Operating line
Range
Factory setting
Outside temperature zone
----, 1...31
----
Heat distribution zone
1...31
1
Heat distr zone source side ----,
1...31
----
Refrigeration distribution zone
1...31
1
Refrig distr zone source side
----, 1...31
----
183 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Communication
01.04.2010