8.1.6
Minimum off time
The minimum switch-off time prevents aggregates from cycling too frequently.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Aggregates > Logic functions Logic 1...10 >
Operating line
Range
Factory setting
Off time minimum
00.00...59.59 m.s
or
*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in Section 8.1.1
The minimum switch-off time always takes effect after a switch-off command.
8.1.7
Operation selector
The operating mode of the logic block output (Preselection) can be preset via the
operation selector in the main menu; the current state is displayed (State). Switch-
on and switch-off delay as well as minimum on and off time are considered.
Main menu > Operation selector 1...10 >
Display values
Operating line
Comment
Preselection
Auto, Off, On.
State
Display of present state: Off, On.
You must first ensure that the operation selector is set to Auto if you want to reset
its configuration later on. Otherwise, the output constantly remains "On" or "Off".
Important note
8.1.8
Wiring test
During the wiring test, the logic block outputs can be directly switched via the
control switch. During the wiring test, delay and on times are inactive.
Main menu > Commissioning > Wiring test > Outputs >
Wiring test
Operating line
Comment
Logic 1…10
Off, On.
8.1.9
Priorities
For logic operations, the following priorities apply:
1. On/Off during wiring test
2. Off by "Off time minimum"
3. On by "On time minimum"
4. Off by "Switch-on delay"
5. On by "Switch-off delay"
6. On by "Operation selector"
7. On by logic inputs
71 / 216