8.5.4
Assign input
Main menu > Commissioning > Extra configuration > Aggregates > Modulating outputs >
Modulating output A...H >
Configuration
Operating line
Adjustable values / Comment
Input 1…
Input 3
---, N.X1, sequence controller x.Rot’step’swi y
(analog values only).
8.5.5
Start condition
Enable the modulating output via a digital signal.
The output signal is issued by considering any limitations.
0 V is issued at the output, or 10 V for inversion, if the start signal is withdrawn.
Maximum selection.
The output is always enabled if there is no start condition.
Main menu > Commissioning > Extra configuration > Aggregates > Modulating outputs >
Modulating output A...H >
Operating line
Adjustable values / Comment
Start condition
---, N.X1, N.X2, ... (digital only).
8.5.6
Assign texts
Assign text to each modulating output.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Aggregates > Modulating outputs > Modulating output A...H >
Operating line
Range
Factory setting
Modulating output A …H
Max. 20 characters
Modulating output A …H
Setting values
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
8.5.7
Function check / wiring test
The current state of the modulating output is displayed on the operator unit.
Main menu > Aggregates > Modulating outputs >
Display values
Operating line
Comment
Modulating output A …H
0...100 %
You can directly control the modulating output during the wiring test.
Main menu > Commissioning > Wiring test > Outputs >
Wiring test
Operating line
Comment
Modulating output A …H
----, 0...100 %
126 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Aggregates
01.04.2010