6.2.2
Event logger settings
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Data acquisition > Event logger > Event logger 1...4 >
Setting values
Operating line
Range
Factory setting
Event logger 1…4
Max. 20 characters
Event logger
1…4
Limit value on
Depending on selected type.
Type-dependent
Limit value off
Depending on selected type.
Type-dependent
Event duration min**
00.00..23.50 h.m
00.00 h.m
Event duration max**
00.00..23.50 h.m
00.00 h.m
Event cycle min**
0...720 h
0 h
Event cycle max**
0...720 h
0 h
Fault priority
Urgent, Not urgent
Not urgent
Geographical zone
(apartment)
1…126 (relevant for "Room
temp via bus")
1
Geographical zone (room) 1…63 (relevant for "Room temp
via bus")
1
Outside temperature zone
1…31 (relevant for "Outside
temp via bus")
1
*
A name can be assigned to the event logger inputs.
** Set the times to 0 to deactivate the individual fault messages.
6.2.3
Event logger display
You can query the last 10 event periods on the display.
They are sorted in chronological order with 1 as the most recent entry.
The data of the event start and end as well as duration for highest
or
lowest
values are displayed as increment key.
The oldest event is deleted if there are more than 10 events.
Main menu > Data acquisition > Event logger 1..4 >
Display values
ON
18.06.2005 00:00
30.06.2005 23:59
40.0°C
18.06.2005 ...
18.06.2005 ...
18.06.2005 ...
19.06.2005 ...
25.0°C
36.8°C
36.8°C
Limit value off
Sa
Maximum
Event logger 1
Entry 1
Entry 1
Entry 1
Entry 1
Mo
Mo
Mo
Maximum
Maximum
Maximum
You can delete event logger entries at the password level.
Main menu > Commissioning > Settings > Data acquisition > Event logger > Event logger
1...4 >
Delete entries
Operating line
Range
Factory setting
Delete logger
No, Yes
No
47 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Data
acquisition
01.04.2010