The trend channels are displayed with their assigned text.
Notes on the display
Trend signal not
available.
The display immediately switches to the 24-hour view if a trend channel is
selected.
The press-and-turn button allows you to navigate between the different views.
6.1.4
Troubleshooting
Trends no longer are recorded if a trend signal
at the local inputs
is no longer
available (e.g. due to a faulty sensor).
In this case, check the fault messages via:
Main menu > Faults > Faults current >
If the values are not available via bus, trends are no longer recorded.
Behavior after power failure
or
after exiting menu "Extra configuration
"
(restart
RMS705B):
Remanent data
The values of the 8-hour and 8-minute views are deleted.
The values of the 24-hour view and those of the last 6 days are retained.
6.2
Event logger
Event logger
Use the event logger to log events and monitor their mandatory occurrence. Event
logging can be activated for max. 4 input variables, e.g. to monitor the minimum
event duration
or
regularity of an event (legionella monitoring).
Purpose
Event logger with 4 inputs.
Function overview
Logging of the last 10 events per logger with time and date stamp upon reaching
value "Limit value on" and Off.
Save max.
or
min. value during event.
Adjustable values for "Limit value on" and Off.
Selectable fault message when below "Event cycle min".
Selectable fault message when above "Event cycle max".
Selectable fault message when below "Event duration min".
Selectable fault message when above "Event duration max".
A name can be assigned to each event logger input.
45 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Data
acquisition
01.04.2010