11 Universal
controller
11.1 Overview
RMS705B provides 3 controllers with 2 sequential outputs each. The universal
controller can provide control to an absolute variable
or
differential variable.
Purpose
11.1.1 Enable the universal controller
Assign an input to the main controlled variable to enable the universal controller.
Main menu > Commissioning > Extra configuration > Controller 1…3 >
Configuration
Operating line
Range
Factory setting
Main controlled variable ---, N.X1, N.X2, ..., internal analog
(analog values).
---
Differential input
---, N.X1, N.X2, ..., internal analog
(analog values).
---
The following settings are required depending on the desired function:
Desired control
Operating line
Setting
Control to an
absolute
variable
(1 sensor input)
Main controlled variable
Differential input
Xx (analog)
---
Control to a
differential
variable
(2 sensor inputs)
Main controlled variable
Differential input
Xx (analog)
Xx (same unit as main controlled variable)
The controller always uses the same unit as the main controlled variable.
Misconfiguration has the following effect:
Operating line
Setting
Type of action
Main controlled variable
Differential input
---
(not relevant)
Controller inactive.
---
Main controlled variable
Differential input
Xx (digital)
(not relevant)
Message sent:
"[Main contr var 1] sensor error"
Main controlled variable
Differential input
Xx (analog)
Xx (other unit as main controlled variable)
Message sent:
"[Main contr var 1] sensor error"
165 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Universal controller
01.04.2010