There are two use cases:
The max. value is monitored and displayed in the event logger under "Maximum" if
"Limit value on" > "Limit value off".
Use case 1: Monitor max.
value
ON
18.06.2005 00:00
30.06.2005 23:59
40.0°C
Sat
Thu
Maximum
Event logger 1
Limit value off
Use case 2: Monitor min.
value
The min. value is monitored and displayed in the event logger under "Minimum" if
"Limit value off" > "Limit value on".
ON
18.06.2005 00:00
30.06.2005 23:59
–12.4°C
Sat
Thu
Minimum
Event logger 1
Limit value off
6.2.1
Activate event logger
Assigning an analog input activates the "Event logger".
Main menu > Commissioning > Extra configuration > Data acquisition > Event logger >
Configuration
Operating line
Range
Factory setting
Input 1
---, N.X1, N.X2, ...
Room temp via bus,
Outside temp via bus
---
Input 2
---, N.X1, N.X2, ...
Room temp via bus,
Outside temp via bus
---
Input 3
---, N.X1, N.X2, ...
Room temp via bus,
Outside temp via bus
---
Input 4
---, N.X1, N.X2, ...
Room temp via bus,
Outside temp via bus
---