An enthalpy value calculated from temperature and relative humidity is available in
RMS705B (device 1). This value is sent as transmission object via an analog
output and handled by the second device.
Example 3
Note
Adjust the value range of the reception terminal (device 2) to the unchangeable
value range of the calculated enthalpy prior to use in device 2. See Section 9.2.1
for the set value range for the enthalpy calculator.
The following transmission and reception zone is engineered for the example:
Data exchange concept
RMS705B, device 1
Device 2
Value
Terminal
Transmission
zone
Terminal
Reception
zone
N.Y1
1
N.X1
1
Enthalpy value for
further use
= Transmission
= Reception
Configuration
C
Device 1 onfigure the following in RMS705B, device 1:
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
Range
Factory setting
N.Y1 1
Configure the following in device 2:
Device 2
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Range
Factory setting
N.X1 kJ/kg
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > N.X1
Setting values
Operating line
Range
Factory setting
Value low
0.0 kJ/kg
- 50.0 kJ/kg
Value high
100.0 kJ/kg
50.0 kJ/kg
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
Range
Factory setting
N.X1 1
KNX
N.Y1
zone 1
Unit 1
Unit 2
MEU
Configuration diagram
189 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Communication
01.04.2010