6.2.4
Fault messages
The following fault messages are generated during violation (above and below) if
the corresponding times for "Event duration min/max"
or
"Event cycle min/max" are
greater than 0.
You must acknowledge these fault messages.
No. Text
Effect
9111
[Logger 1] on before cycle min
Fault priority as set;
must be acknowledged and reset.
9112
[Logger 1] on after cycle max
Fault priority as set;
must be acknowledged and reset.
9113
[Logger 1] off before dur min
Fault priority as set;
must be acknowledged and reset.
9114
[Logger 1] off after dur max
Fault priority as set;
must be acknowledged and reset.
9121
[Logger 2] on before cycle min
Fault priority as set;
must be acknowledged and reset.
9122
[Logger 2] on after cycle max
Fault priority as set;
must be acknowledged and reset.
9123
[Logger 2] off before dur min
Fault priority as set;
must be acknowledged and reset.
9124
[Logger 2] off after dur max
Fault priority as set;
must be acknowledged and reset.
9131
[Logger 3] on before cycle min
Fault priority as set;
must be acknowledged and reset.
9132
[Logger 3] on after cycle max
Fault priority as set;
must be acknowledged and reset.
9133
[Logger 3] off before dur min
Fault priority as set;
must be acknowledged and reset.
9134
[Logger 3] off after dur max
Fault priority as set;
must be acknowledged and reset.
9141
[Logger 4] on before cycle min
Fault priority as set;
must be acknowledged and reset.
9142
[Logger 4] on after cycle max
Fault priority as set;
must be acknowledged and reset.
9143
[Logger 4] off before dur min
Fault priority as set;
must be acknowledged and reset.
9144
[Logger 4] off after dur max
Fault priority as set;
must be acknowledged and reset.
Fault messages
6.2.5
Troubleshooting
Changing the current data
or
time during event logging may result in premature
triggering of a fault message.
Notes
After changing the extra configuration in the event logger, previous logs are
deleted when the extra configuration is closed.
No event logging takes place if "Limit value on" = "Limit value off".
48 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Data
acquisition
01.04.2010