6.4.6
Display meter readings
The current meter reading, the date and the reading of the last 15 months are
displayed.
Main menu > Data acquisition > Meter 1...4 >
Display values
Operating line
Comment
Meter reading current
0…999'999’999
Unit
As per the configured display format.
[Readout 1] date
[Readout 1] meter reading
…
[Readout 15] date
[Readout 15] meter reading
The listed operating lines also exist for meters 2 to 4.
Notes
The monthly values are stored at midnight at the end of the month.
The 15 monthly values can be deleted at the password level via operating line
"Reset monthly values".
6.4.7
Assign texts
A specific text can be assigned to each meter. This text is displayed as menu and
operating line text on the operating pages.
Main menu > Commissioning > Settings …
or
Free text
Main menu > Settings > Data acquisition > Meter > Meter 1...4 >
Operating line
Range
Factory setting
Meter 1…4
Max. 20 characters
Meter 1…4
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
6.4.8
Troubleshooting
Some battery-powered
or
mechanical meters continue metering in the event of a
power failure. During a power failure affecting RMS705B, the pulses are not
counted.
A restart occurs after you exit menu "Extra configuration". Pulses received between
the last storage operation and restart (max. 5 minutes) are not counted.