Average temperature measurement with 4 passive sensors using LG-Ni1000
sensing element.
Example 3
Main menu > Commissioning > Extra configuration > Input identifier >
Input configuration
Operating line
Setting
N.X1 °C
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line
Setting
Type Ni1000
Connection diagram
G
G
G0
X...
M
G0
B...
N
31
23
A
08
A
C
24 V
B
M
LG-Ni 1000
B
M
LG-Ni 1000
B...
B...
B
M
LG-Ni 1000
B
M
LG-Ni 1000
B...
B… Passive
sensor
5.2.6
Troubleshooting
When you exit the "Commissioning" menu, a check is made to see which sensors
are connected. Message "[...X...] sensor error" is displayed if one of the sensors
connected at this point is missing later on
or
if there is a short-circuit.
If there is no measured value due to an open-circuit, the display reads: ----
If there is no measured value due to a short-circuit, the display reads:oooo
No. Text
Effect
101…
264
[N.X1] sensor error …
RMZ788(2).X4 sensor error
Non-urgent message; must not be
acknowledged.
Fault messages
34 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Inputs