The air quality average value of 2 air quality sensors is available in RMS705B
(device 1). This value is sent as transmission object via an analog output and
handled by RMS705B (device 2).
Example 1
The following transmission and reception zone is engineered for the example:
Data exchange concept
RMS705B, device 1
RMS705B, device 2
Value
Terminal Transmission
zone
Terminal Reception
zone
N.Y1
1
N.X1
1
Air quality average
= Transmission
= Reception
Configuration
Device 1
Configure the following in RMS705B, device 1:
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
Range Factory
setting
N.Y1 1
Configure the following in RMS705B, device 2:
Device 2
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Range
Factory setting
N.X1 ppm
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
Range
Factory setting
N.X1 1
Configuration diagram
X
KNX
N.Y1
zone 1
Unit 1
Unit 2