9.1.2
Modulating output settings
You can set the value range mapping the DC 0…10 V signal (Y) at block "Min-Max-
Average". To do this, set the lower (0 V) and upper (10 V) value. RMS705B linear
calculates interim values accordingly (see diagram below).
The value range setting mapped to the DC 0…10 V signal (Y) does not impact the
internal, analog output signal (a).
Note
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Signal converter > Min-Max-Average 1…2 >
Operating line
Range
Factory setting
Value low A
Depending on selected type
0%, 0°C, type-dependent
Value high A
Depending on selected type
100%, 50°C, type-dependent
Value low B
Depending on selected type
0%, 0°C, type-dependent
Value high B
Depending on selected type
100%, 0°C, type-dependent
0 V
10 V
Value low A
9.1.3
Input 1 weighting factor
The value for "Input 1" can be weighted by factor x when calculating the average
value.
Value at "Input 1" can be weighted double, triple to 100x the values of the
remaining inputs.
X-weighted "Input 1" is counted as several inputs for calculation.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Signal converter > Min-Max-Average 1...2 >
Operating line
Range
Factory setting
Factor input 1
1 … 1 0 0
1
Entry:
Example
–
Factor input 1": 5
–
Provide signals to the remaining 4 inputs.
Result:
The output provides the average value of 9 (5 + 4) input signals.
128 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Signal
converter
01.04.2010