Main menu > Commissioning > Extra configuration > Input identifier >
Configuration
Operating line
Adjustable values / Comment
N.X1
Activate the function by assigning the following to the
input: Outside temperature, °C, %, g/kg, kJ/kg, W/m²,
m/s, bar, mbar, Pa, ppm, Universal 000.0, Universal
0000, digital,
or
pulse.
...
ditto
RMZ788(2).X4
ditto
Comments
The outside temperature unit is always °C.
Identifiers °C, %, g / kg, kJ / kg, W / m², m / s, bar, mbar, Pa, ppm, Universal 000.0
and Universal 0000 are always analog inputs.
Digital inputs do not require a unit (On/Off).
The outside temperature can be sent via bus (KNX) (see Section 5.6 "Outside
temperature").
5.1.2
Cause
The source of an input value is displayed. We differentiate among the following
types:
Terminal: Used as local terminal.
LTE mode: Used as LTE transmission and reception object.
S-mode: Used as S-mode object.
Simulation: Input terminal simulation.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Operating line
Range
Factory setting
Cause
Terminal, LTE mode, S-
mode, Simulation
Section 13.2.5 explains LTE transmission and reception objects.
Note
29 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Inputs
01.04.2010