5.3.2
Texts for logical states 0 and 1
A free text can be assigned to each digital input for logical states 0 and 1 (e.g.
On/Off, full/empty, etc.). The text is displayed after it is assigned to the
corresponding input.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line
Range
Factory setting
Text for: Logic 0
Max. 20 characters
0
Text for: Logic 1
Max. 20 characters
1
5.3.3
Connection example
Potential-free contacts can be connected to the digital inputs.
Main menu > Commissioning > Extra configuration > Input identifier >
Input configuration
Operating line
Setting
N.X2 Digital
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line
Setting
Normal position
Open
G
G
G0
X...
G0
N
31
23
A
09
A
C
24 V
M
F...
p
X...
M
F...
Connection diagram
F…
Detector with potential-free switching contact.
36 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Inputs
01.04.2010