Split function "Inputs split" is enabled.
Example
A-Average-, B-Max
calculation
N.X1
N.X2
N.X3
N.X4
A
N.Y1
° C
° C
%
%
X
X
X
312
4S
1
9e
n
Function range A:
"Min-Max-Average" block calculates the average from terminal values N.X1, N.X2
(both in °C). The result is used as internal, analog signal (a) from controller 1 as
main control variable.
Function range B:
"Min-Max-Average" block calculates the maximum from terminal values N.X3, N.X4
(both in %). The result (as % value) is used as internal, analog signal (a) from
controller 1 as "Universal shift".
129 / 216