8.5.2
Limitations
The modulating output (Y) can be limited at the top and bottom.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Aggregates > Modulating outputs > Modulating output A...H >
Operating line
Range
Factory setting
Positioning signal min
0...100 %
0 %
Positioning signal max
0...100 %
100 %
Output 0...100 % then corresponds to "Positioning signal min" (Ymin) to
"Positioning signal max" (Ymax).
0 %
100 %
0 %
0 V
100 %
10 V
Y
Y
max
min
Y
Qs
31
23
D
09
Y´
Function diagram
Qs
= Load demand from controller
Y´ =
Inversion
Key
You can thus parameterize the output with a DC 5...7.5 V input suitable for
controlling a magnetic valve, for example.
The greater of the signals is valid (maximum selection) when the modulating output
of 3 controllers is controlled.
Maximum selection
8.5.3
Output inversion
Any output can be inverted.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Aggregates > Modulating outputs > Modulating output A...H >
Operating line
Range
Factory setting
Inversion No,
Yes
No
Meaning:
No:
0...100% load = 0...100% output.
Yes:
0...100% load = 100...0 % output.
125 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Aggregates
01.04.2010