The event is saved in the event logger only after processing "Limit value off".
Data of the current event is lost if preceded by a power failure. Previously saved
events remain available.
Logging is canceled and terminated if the measured value signal at the terminal
is no longer available. Logging is resumed after the signal is reactivated.
The previous event cycle is not saved if yet another event cycle occurs within 5
minutes.
6.3
Operating hours
Operating hours
The following 4 operating hours counters are available:
Purpose
They use a digital input signal to record the operating hours of any aggregate.
Operating hours since last maintenance are counted in addition to total
operating hours.
RMS705B generates a freely definable maintenance message when the
maintenance interval value is reached.
Counters "Operating hours since service" continue to run until reset to 0 via
"Reset".
Resetting counter "Operating hours since service" does not impact the
counter for total operating hours.
The maintenance messages for the operating hours counter are displayed as
part of the fault message "Main menu > Faults".
A name can be assigned to each operating hours counter.
The counter can be set to any start value at the password level.
The following figure provides a visual description of the above functionality:
Maintenance messages
for the operating hours
counter
Service
interval
Service
message
Service
message
Hours run
Hours run
since service
Reset
Reset
49 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Data
acquisition
01.04.2010