Description, device design, dimension drawing
2.6 Displays
PSU8600power supply systems
32
Manual, 04.2016, A5E35883207-7-76
Table 2- 8
LED "ON/OFF/RST"
⑥
Signaling
Off
•
Device is off or is powering up (booting)
•
Or parallel connection function is active (only output 2 and/or 4)
•
Or ERROR OFF shutdown
•
Or incorrect hardware configuration (REMOTE mode)
•
Or firmware being updated/completed
Green
Normal operation, output current < response threshold value
Flashing green (0.25/0.25)
Overload at the output: Output current 101…150 % of the response threshold
(operation permissible up to 149 % for 5 s, 150 % for 200 ms
Flashing green (1/1)
For overload, the output current is limited
•
To the response threshold value for the duration of the overload (CONSTANT
CURRENT mode)
•
to the rated value for 60 s for system overload
Red
Output automatically shut down due to
•
Overload exceeding the permissible time range (ELECTRONIC SHUTDOWN
mode)
•
Output 1 prioritized for buffer mode
•
Overtemperature of the output (in pairs)
Flashing red (0.25/0.25)
After automatic shutdown due to overload or overtemperature, output is ready for
reset by pressing the button, reset signal or control command
Flashing red (1/1)
Output shut down via control command (REMOTE mode)
Yellow
Output manually shut down using the button at the device
Table 2- 9
LED "PARALLEL"
⑦
Signaling
Off
•
Device is OFF or is powering up (booting)
•
Device is operational and the parallel connection function is not activated
Green
Parallel connection function activated
Flashing green (1/1)
Parallel connection function activated; wiring fault identified
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...