Operator control at the device
3.3 Overload shutdown and carrying out a reset
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
57
Carrying out a reset with the button at the device
An individual output can be reset using the button. This resets the electronic shutdown of the
output, caused by an overload condition.
①
Output number
②
Button (illuminated with an LED)
The initial situation is an electronic shutdown as a result of an overload condition. This is
signaled using LED "ON/OFF/RST" in button
②
:
LED in the but-
ton
Meaning/handling
Lit red
Electronic shutdown as a result of an overload; wait time until a reset is possible:
5 seconds.
Flashes red
Output ready for a reset; press the button to switch-on the output again.
Lit green
The reset was carried out, the output was switched-on again.
Procedure
1.
After an electronic shutdown (LED "ON/OFF/RST" of the output is lit red), allow a wait
time of 5 seconds to elapse.
2.
Press the button of the output, which is ready for a reset (LED "ON/OFF/RST" of the
output flashes red).
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...