Engineering and remote access
7.4 SIMATIC STEP 7
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
161
7.4.5
Loading the configuration (commissioning)
In the delivered state, the SITOP PSU8600 has not yet been assigned any IP address and
the DHCP protocol is deactivated.
When the SITOP PSU8600 is first connected with a controller (SIMATIC S7 control), it must
be assigned a device name and an IP address by the controller. A new configuration can be
loaded to the device with STEP 7.
Preconditions
●
The SITOP PSU8600 has been correctly connected and linked with the network.
●
PG/PC with STEP 7 is connected with the network.
Displaying accessible nodes
Note
If nodes can only be accessed via interposed switches or routers (with protocol conversion),
they are not displayed in the list of the accessible nodes.
1.
Click in the "Target system" menu on "Display accessible nodes"
The "Accessible nodes" window is opened with the following displays:
–
The station
–
The SITOP PSU8600
The following table shows which information is displayed in the "Object name" column.
Accessible nodes
Object name
Description
S7-CPU, PC station
Name of the station
The "Details" view also shows the operating
state, module type and, if available, information
from the associated STEP 7 project (station
name, CPU name, system identification).
Initially loading the IO controller
Once you have configured the SITOP PSU8600 and the station, you must load this
configuration into the IO controller (SIMATIC S7 control system). This is the way that the IO
controller is assigned its configured IP addresses.
Before loading, carry out a consistency test to check the configuration for duplicate
addresses, identical names, etc.
Inform yourself whether the IO controller to be loaded can also be initially loaded via the
PROFINET interface. If not, you must first load the hardware configuration via the MPI
interface.
1.
Select in the "Target system > Load" menu.
2.
Select the module to be loaded.
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...