Installation
6.1 Line-side connection
PSU8600power supply systems
108
Manual, 04.2016, A5E35883207-7-76
Protection
Protection for 6EP3436-8MB00-2CY0
Protection required
•
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 6 ... 16 A
or
•
Should 3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent release: 3 A
or
•
3RV2711-1DD10 circuit breaker (branch circuit protection acc. to UL 489)
Protection for 6EP3437-8MB00-2CY0
Protection required
•
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 10 ... 16 A
or
•
3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent release: 3 A
or
•
3RV2711-1DD10 circuit breaker (branch circuit protection acc. to UL 489)
The protective conductor of the line supply must be connected at the "PE" terminal.
Other country-specific regulations may have to be observed when installing the device.
Also observe the information in Section Connections and terminal designations (Page 21).