Installation and maintenance
4.6 System response for a modified hardware configuration
PSU8600power supply systems
94
Manual, 04.2016, A5E35883207-7-76
4.6.2
Response after adding an individual component
Adding involves expanding the system on the right-hand side by adding additional
components.
Note
When changing the module sequence, by checking the module position it is possible that
previously used modules are undesirably deactivated – and outputs that have been used up
until now are shutdown.
To avoid undesirably deactivating modules that have been used up until now – and shutting
down outputs that have been used up until now, insert the new individual components at the
right-hand side of the system. As a consequence, the previous module sequence in the
system configuration is not changed.
Response after adding a component and powering up in the MANUAL mode
●
New buffer modules are automatically commissioned.
●
For new expansion modules, after switching on again, the outputs are in the operating
state "manually shut down" (the LEDs of the outputs are lit yellow).
The outputs are switched-on by pressing their associated buttons.
Response after adding a component and powering up in the REMOTE mode
●
The new module is deactivated (LED "OK" flashes red, LEDs of the expansion module
outputs are dark).
You can activate the module by loading a correct configuration via the associated control
system.
4.6.3
Response after removing an individual component
NOTICE
Incorrect response and damage after switching on again
Different settings and incorrect wiring, that can be caused by changes made to the system
configuration, can result in an incorrect response and subsequent damage.
After making any change to the system configuration, ensure the correct settings of the
remaining components as well as the correctness of the associated wiring to avoid any
incorrect response and damage after switching on again.
Note
By removing modules, it is possible that the previous module position of the remaining
modules is changed. This can result in modules, whose position has changed, being
deactivated and outputs shutdown.
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...