Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
210
Manual, 04.2016, A5E35883207-7-76
Data
Description
Data type
Channel1 Ilimit
[10 mA]
Response threshold of the output current for output 1. When this is exceeded,
the output current is interpreted as having an overload condition and is shut
down with a time delay - or limited.
Unsigned16
Channel1 Ithreshold
(0-100 %)
Prewarning threshold of the configured response threshold for the output cur-
rent in %. An alarm is initiated when the actual output current exceeds this
value. Operation is continued without any restrictions. Prewarning is deactivat-
ed by entering "0 %".
Unsigned8
Fill byte [s]
-
Unsigned8
Channel1 output
voltage [10 mV]
Output voltage at output 1.
Unsigned16
Channel1 output
current [10 mA]
Output current at output 1.
Unsigned16
Channel1 max output
current 10 mA]
Maximum output current at output 1.
Unsigned16
Channel1 Operation
mode
Operating mode output 1:
If the actual load current
of an output exceeds the
specified response
threshold value of the
output current, then the
output can be shut down
according to a current-
time characteristic ("elec-
tronic shutdown"), or the
load current can be lim-
ited to the response
threshold ("constant cur-
rent").
0 = ModeSelect
Electronic shutdown: The
output is shut down when
the response threshold
value is exceeded.
Unsigned8
1 = ModeModular
Constant current: When
the response threshold
value is exceeded, the
load current is limited to
the response threshold
until this is fallen below
again.
Channel1 parallel
mode (0/255)
Actual parallel connection for output:
•
0 = parallel connection deactivated
•
255 = parallel connection activated
Unsigned8
Channel1 operation
state
Operating state output 1
0 = ManualOff
Output switched off man-
ually (button):
Unsigned8
1 = RemoteOff
Output switched off
(PROFINET/IE):
2 = BufferOff
Output switched off
3 = OverLoadOff
Output switched off (over-
load):
4 = ReadyForRestart
Output ready for reset:
5 = ErrorOff
Output switched off (fault)
6 = Boot
Output switched off (pow-
ering up)
7 = Running
Output switched on (nor-
mal operation)
8 = OverLoad
Output in overload opera-
tion:
9 = Limit
Output current limited to
the response threshold:
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...