Troubleshooting
8.2 PROFINET alarm list
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
225
Output error
257
15
F
Invalid number of modules
Invalid number of modules detected.
Invalid slot.
257
16
MR
New unconfigured module detected
New unconfigured module detected.
257
17
F
Invalid system configuration
System configuration is incorrect. Normal
operation of the system is not possible.
257
18
MD
Deviating system configuration
System configuration is different. Devia-
tions from the expected response may
occur outside normal operation.
257
19
MR
Invalid system configuration
System configuration is different. The
system can be operated.
257
20
F
Unclassified hardware fault
Unclassified hardware fault has occurred.
All outputs of the power supply system
have been switched off.
257
21
F
Invalid parameter
Faulty parameter detected.
257
22
F
Unknown parameter
Unknown parameter detected.
257
23
F
Invalid parameter.
Invalid parameter value transferred.
257
24
F
Invalid parameter
Invalid parameter
257
25
MR
Module with excessive power detected
A module with excessive power was
detected. Normal system operation is
possible.
257
26
MR
Unexpected module type detected
Unexpected module type detected.
257
27
MD
Module with reduced power detected.
A module with reduced performance was
detected. A different system response is
possible.
257
28
F
Incompatible module detected
The module type is incompatible to the
configuration. The module cannot be
commissioned.
257
29
F
Unexpected empty slot detected
Unexpected empty slot detected.
257
30
MR
Short time interruption for output 1 was
activated
The short time interruption function for
output 1 was activated. As soon as buffer
operation of the supply voltage returns,
the voltage at output 1 is interrupted for
the defined duration. However, the short
time interruption is realized at the earliest
after the defined wait time expires.
257
31
MR
Buffer operation deactivated via control
contact
The buffer readiness of all of the buffer
components in the system were deac-
tivated by an external hardware control
contact.
258
-
F
Fault at the output
Fault at the output
258
1
F
Overload shutdown of the output
Inadmissible overload at the output has
occurred. The output was shut down.
258
2
MD
Overload detected at the output
Output current at the output is still within
the permissible overload profile based on
specified response threshold.
258
3
MR
Overload detected at the output
Output current is above the specified
warning threshold. Operation can contin-
ue without restrictions.
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...