Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
195
Detailed information about the individual operating states can be found in Section Operating
states SITOP CNX8600 (Page 199)
Input data SITOP BUF8600
SITOP BUF8600 100 ms/40 A and SITOP BUF8600 300 ms/40 A
Slot
Subslot Data
Description
Data size
1-16
1
Fill byte(s)
-
Unsigned16
Fill byte(s)
-
Unsigned16
Fill byte(s)
-
Unsigned16
Fill byte(s)
-
Unsigned16
Buffer operation state
Operating state of the buffer module
SITOP BUF8600.
Unsigned8
SITOP BUF8600 4 s/40 A and SITOP BUF8600 10 s/40 A
Slot
Subslot Data
Description
Data size
1-16
1
Fill byte(s)
-
Unsigned16
Fill byte(s)
-
Unsigned16
Fill byte(s)
-
Unsigned16
Fill byte(s)
-
Unsigned16
Buffer operation state
Operating state of the buffer module
SITOP BUF8600.
Unsigned8
Charging state [0-100%]
Charge state of the buffer module
SITOP BUF8600.
Unsigned8
Buffering disabled by input [0/255]
Buffer module SITOP BUF8600 was
deactivated via the control contact.
Unsigned8
Detailed information about the individual operating states can be found in Section Operating
states SITOP BUF8600 (Page 200)
7.6.1.2
Output data
In the following tables you can find an overview of the output data, which is cyclically sent
from the PROFINET IO-Controller to the SITOP PSU8600 and the expansion modules.
Output data SITOP PSU8600
Slot
Subslot Data
Description
Value range
Data size
0
2
Device Reset_In
Status of input "Reset_In": This
input resets all active faults and
reactivates all of the outputs that
are in the "Ready for restart" oper-
ating state.
0 = false, 0 <> true
(default setting: false)
Unsigned8
Device Ithreshold
[1 %]
Prewarning threshold total current
of the SITOP PSU8600.
0 - 100 %
(default setting: 90 %)
Unsigned8
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...