Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
199
Operating state output 1... 4 (Channel1...4 operating state)
The status messages of an output are listed in the table below. The data applies to outputs 1
to 4.
Status message
Description
0 = ManualOff
Output switched off manually (button): The output was manually switched off using the
button on the device. The device can only be switched on manually using the button on the
device.
1 = RemoteOff
Output switched off (PROFINET/IE): The output was remotely switched off via
PROFINET/IE.
2 = BufferOff
Output switched off (prioritization output 1): The output was switched off during buffer oper-
ation.
3 = OverLoadOff
Output switched off (overload): Inadmissible overload at the output has occurred. The out-
put was switched off.
4 = ReadyForRestart
Output ready for reset (reset): Output is ready to be switched on again after automatic over-
load shutdown.
5 = ErrorOff
Output switched off (fault)
6 = Boot
Output switched off (powering up)
7 = Running
Output switched on (normal operation)
8 = OverLoad
Output in overload operation: The output current is above the specified response threshold,
but still within the permissible overload profile.
9 = Limit
Output current limited to the response threshold: The output is in the overload mode. The
output current is limited to the configured response threshold.
10 = OverloadDerate
Output in overload operation (with derating):
11 = LimitDerate
Output current limited (with derating)
7.6.1.4
Operating states SITOP CNX8600
Operating state of an expansion module (module operating state)
Status message
Description
0 = Off
Expansion module is switched off
1 = ErrorOff
The expansion module was automatically shut down as a result of operation under inad-
missible operating conditions.
2 = CooledDown
After an automatic shutdown due to a fault, the expansion module can be reactivated by
switching off and switching on the supply voltage.
3 = Boot
The expansion module is powering up, all of the outputs are still switched off.
4 = Running
The expansion module is operating in the normal mode.
5 = Buffering
Primary supply voltage has failed. The expansion module is operating in the buffer mode.
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...