Engineering and remote access
7.5 Web server
PSU8600power supply systems
186
Manual, 04.2016, A5E35883207-7-76
expanding the system. As a consequence, using the prewarning threshold increases the
operational reliability.
Enter a value of "0 %" to deactivate the prewarning threshold.
●
Prewarning threshold output current in the MANUAL mode
Here, it is possible to define a common threshold value for all outputs, above which an
alarm is output.
Enter a value of "0 %" to deactivate the prewarning threshold.
●
Dead time for system overload alarm
A system overload alarm is only initiated if a continuous system overload occurs, which is
longer than the set dead time.
●
Dead time for power supply failure alarm
A buffer operation alarm is only initiated if the power continuously fails for a time that is
longer than the set dead time.
PROFIenergy parameters
Parameters
Value range
Default setting
Enable PROFIenergy on this device
Yes/no
No
Time to pause
0 - 2147483647
0 ms
Time to operate
0 - 2147483647
0 ms
Time min length of stay
0 - 2147483647
0 ms
Time max length of stay
0 - 2147483647
0 ms
Save power consumption
0.000 - 100000.000
0.00 kW
Operate power consumption
0.000 - 100000.000
0.00 kW
Energy consum to pause
0.000 - 100000.000
0.00 kWh
Energy consum to operate
0.000 - 100000.000
0.00 kWh
Procedure
1.
Select the "Hardware configuration" menu.
2.
Select submenu "Device configuration".
3.
Select entry "PSU8600".
4.
Make the required settings in the editor area.
5.
Load the data to the device, see Loading the configuration (commissioning) (Page 170).
You can find additional information on configuring the outputs in Chapter Operator control at
the device (Page 51).
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...