Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
207
Data
Description
Data type
Ilimit3 potentiometer [10mA]
Manually set threshold of the output current at
output 3. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable3 manual button (0/255)
Actual DIP switch state for output 3:
•
0 = Manually shut down
•
255 = Manually switched on
Unsigned8
Fill byte[s]
-
Unsigned8
Utarget4 potentiometer [10 mV]
Manually set setpoint of the output voltage at out-
put 4: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit4 potentiometer [10 mA]
Manually set threshold of the output current at
output 4. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable4 manual button (0/255)
Actual DIP switch state for output 4:
•
0 = Manually shut down
•
255 = Manually switched on
Unsigned8
Fill byte[s]
-
Unsigned8
ModuleIdentNumber slot0/MainUnit
Module identification number for slot 0 (basic de-
vice).
Unsigned32
ModuleIdentNumber slot 1
Module identification number for slot 1.
Unsigned32
ModuleIdentNumber slot 2
Module identification number for slot 2.
Unsigned32
ModuleIdentNumber slot 3
Module identification number for slot 3.
Unsigned32
ModuleIdentNumber slot 4
Module identification number for slot 4.
Unsigned32
ModuleIdentNumber slot 5
Module identification number for slot 5.
Unsigned32
Index 0x0008: Buffer handling values (reading/writing)
Data
Description
Data type
Buffer Disable (0/255)
Activating/deactivating buffer readiness.
Unsigned8
LongLife Mode (0/255)
Activating/deactivating the "Long Life" mode.
Unsigned8
ChargeReadyThreshold [ms]
Threshold value for sufficient buffer readiness
Unsigned16
PowerInterrupt Enable (0/255)
Activating/deactivating brief interruption of the
power supply for output 1. In this case, output 1 is
switched off for a defined time.
Unsigned8
Fill byte[s]
-
Unsigned8
PowerInterrupt DeadTime [ms]
Time delay with which the brief interruption of the
power supply for output 1 is started.
Unsigned16
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...