Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
200
Manual, 04.2016, A5E35883207-7-76
Operating state output 1... 4 (Channel1...4 operating state)
The status messages of an output are listed in the table below. The data applies to outputs 1
to 4.
Status message
Description
0 = ManualOff
Output switched off manually (button): The output was manually switched off using the
button on the device. The device can only be switched on manually using the button on the
device.
1 = RemoteOff
Output switched off (PROFINET/IE): The output was remotely switched off via
PROFINET/IE.
2 = BufferOff
Output switched off (prioritization output 1): The output was switched off during buffer oper-
ation.
3 = OverLoadOff
Output switched off (overload): Inadmissible overload at the output has occurred. The out-
put was switched off.
4 = ReadyForRestart
Output ready for reset (reset): Output is ready to be switched on again after automatic over-
load shutdown.
5 = ErrorOff
Output switched off (fault).
6 = Boot
Output switched off (powering up).
7 = Running
Output switched on (normal operation)
8 = OverLoad
Output in overload operation: The output current is above the specified response threshold,
but still within the permissible overload profile.
9 = Limit
Output current limited to the response threshold: The output is in the overload mode. The
output current is limited to the configured response threshold.
10 = Overloaded
AfterSystemOverload
Output in overload operation (system overload).
11 = LimitAfter
SystemOverload
Output current limited (system overload).
7.6.1.5
Operating states SITOP BUF8600
Operating state of the buffer module (buffer operating state)
Status message
Description
0 = Off
Buffer component is in the "Off" operating state.
1 = Boot
Buffer component is powering up.
2 = Full
Complete buffer readiness: The energy storage device of the buffer component is fully
charged (normal operation).
3 = Buffering
The buffer component is operating in the buffer mode: The power supply system is supplied
via the buffer component(s).
4 = ErrorOff
Shutdown after an error: A fault/error has occurred when operating the buffer component.
The buffer component is not operational and must be restarted by switching off the supply
voltage and switching it on again.
5 = NotFully
ChargedReady
Ready for buffer operation as the energy storage device of the buffer module has been
sufficiently charged.
6 = NotFully
ChargedNotReady
Not ready for buffer operation as the energy storage device of the buffer module has not
been sufficiently charged and is presently being charged.
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...