Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
214
Manual, 04.2016, A5E35883207-7-76
Data
Description
Data type
Operation Mode
Mode: If the actual load
current of an output ex-
ceeds the specified re-
sponse threshold value of
the output current, then
the output can be shut
down according to a cur-
rent-time characteristic
("electronic shutdown"),
or the load current can be
limited to the response
threshold ("constant cur-
rent").
0 = ModeSelect
Electronic shutdown: The
output is shut down when
the response threshold
value is exceeded.
Unsigned8
1 = ModeModular
Constant current: When
the response threshold
value is exceeded, the
load current is limited to
the response threshold
until this is fallen below
again.
Startup Delay [ms]
ON delay Individual delay time for the output, referred to a common starting
point. Only valid for system switch-on behavior "Variable on delay".
Unsigned16
Index 0x0006: Device information (reading)
Data
Description
Data type
MLFB / Order number
Article No. / Order number
VisibleString(20)
Product state
Product release
Unsigned8
Fill byte(s)
-
Unsigned8
SW version
Software version
Unsigned32
Serial number
Serial number
VisibleString(16)
Index 0x0007: Hardware settings (reading)
Data
Description
Data type
Utarget1 potentiometer [10mV]
Manually set setpoint of the output voltage at out-
put 1: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit1 potentiometer [10mA]
Manually set threshold of the output current at
output 1. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
Unsigned16
Output Enable1 manual button (0/255)
Actual DIP switch state for output 1:
•
0 = Manually shut down
•
255 = Manually switched on
Unsigned8
Fill byte(s)
-
Unsigned8
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...