Engineering and remote access
7.6 Cyclic and acyclic data
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
209
Data
Description
Data type
1 = ErrorOff
The power supply system
was automatically shut
down as a result of opera-
tion under inadmissible
operating conditions.
2 = CooledDown
After an automatic shut-
down due to a fault, the
power supply system can
be reactivated by switch-
ing off and switching on
the supply voltage.
3 = Boot
The power supply system
is powering up, all of the
outputs are still switched
off.
4 = Running
The power supply system
is operating in the normal
mode.
5 = Phasefail
Phase failure of the sup-
ply voltage detected. The
power supply system can
continue to operate in the
normal mode without any
restrictions for a limited
period of time.
6 = SystemOverload
(IP)
System overload detected
within the permissible
overload profile. The
power supply system is
still operating in the nor-
mal mode.
7 = SystemOverload
(OP)
System overload detected
outside the permissible
overload profile. Power
supply system only oper-
ating with some re-
strictions.
8 = SystemOverload
(PL)
Very high, brief load peak
detected. Power supply
system is operating in the
normal mode.
9 = Buffering
Primary power supply
voltage has failed. Power
supply system is in the
buffer mode.
Ua_OK (0/255)
State of output "UA-OK relay" : Indicates whether all of the power supply sys-
tem output voltages are correct.
Unsigned8
Max device output
current [10 mA]
Maximum output current of the power supply system.
Unsigned16
Channel1 Utarget
[10 mV]
Currently set setpoint of the output voltage for output 1.
Unsigned16
Содержание SITOP BUF8600
Страница 6: ...Overview PSU8600power supply systems 6 Manual 04 2016 A5E35883207 7 76 ...
Страница 12: ...Safety instructions PSU8600power supply systems 12 Manual 04 2016 A5E35883207 7 76 ...
Страница 164: ...Engineering and remote access 7 4 SIMATIC STEP 7 PSU8600power supply systems 164 Manual 04 2016 A5E35883207 7 76 ...
Страница 240: ...Technical data 9 9 Dimension drawings PSU8600power supply systems 240 Manual 04 2016 A5E35883207 7 76 ...
Страница 246: ...Environmental conditions PSU8600power supply systems 246 Manual 04 2016 A5E35883207 7 76 ...
Страница 250: ...Environment PSU8600power supply systems 250 Manual 04 2016 A5E35883207 7 76 ...